Electrical Cabinet Pyrolysis Particle, Temperature & Humidity Detector with Modbus RTU SCADA Integration

AT-AS05 monitors pyrolysis particles, temperature and humidity inside electrical cabinets and supports RS485 Modbus RTU integration with PLC and SCADA systems for centralized early fire warning and condition monitoring.
Electrical Cabinet Pyrolysis Particle, Temperature & Humidity Detector with Modbus RTU SCADA Integration
Case Details


Electrical Cabinet Pyrolysis Particle, Temperature & Humidity Detector with Modbus RTU SCADA Integration

Electrical fires do not always begin with visible smoke or open flame. In many electrical cabinets, switchgear panels, battery enclosures and control cabinets, the first stage of a developing fire can be abnormal heating of cables, insulation materials, breakers, switches or other electrical components.

As temperature continues to rise, materials such as PVC insulation, ABS and other electrical insulating materials may begin to thermally decompose and release extremely small pyrolysis particles and gases before visible smoke develops.

The ANWETECH AT-AS05 Electrical Cabinet Pyrolysis Particle Detector is designed to monitor this early stage of electrical overheating while also providing temperature and humidity monitoring and digital communication through RS485 Modbus RTU.

This allows the detector to operate not only as a local early-warning device, but also as a monitoring node that can be integrated into PLC and SCADA-based industrial monitoring systems.

The AT-AS05 documentation specifies monitoring of pyrolysis particles produced by overheating electrical materials before visible smoke develops. Typical monitored sources include PVC insulated cables, ABS materials, batteries, circuit breakers and load switches. 


1. Why Detect Pyrolysis Particles Inside Electrical Cabinets?

A conventional smoke detector normally responds after sufficient combustion products or visible smoke have developed.

Electrical overheating, however, can begin much earlier.

A typical progression may be:

Loose connection / overload / component overheating

↓

Local temperature rise

↓

Electrical insulation begins to thermally decompose

↓

Pyrolysis particles and decomposition products are generated

↓

Visible smoke develops

↓

Ignition or fire

AT-AS05 is intended to detect changes associated with the thermal decomposition stage.

According to the product documentation, the detector is capable of monitoring particles generated during overheating and decomposition, including particles described in the approximate 1 nm to 10 nm range, before visible smoke is produced. 3f9ba5c7-ddce-450d-8426-30baf30…

This makes the detector particularly relevant for enclosed electrical environments where abnormal heating may develop internally before smoke becomes visible outside the cabinet.


2. What Does AT-AS05 Monitor?

One of the main characteristics of AT-AS05 is that it does not rely only on a single alarm indication.

Its Modbus communication map provides separate monitoring channels for pyrolysis particles, temperature and humidity.

Pyrolysis Particle Monitoring

Channel 1 is assigned to pyrolysis particle detection.

Through the Modbus input registers, the supervisory system can access:

  • Detector channel status
  • Pyrolysis particle alarm setpoint
  • Actual pyrolysis particle measured value
  • Contamination level

The protocol identifies the detector type as a Pyrolysis Particle Detector and provides dedicated registers for Channel 1 status, alarm threshold and measured value. 

This is important for SCADA applications because the supervisory system does not have to depend only on a final alarm relay. It can obtain actual detector data through digital communication.


3. Temperature Monitoring

AT-AS05 also provides temperature-related monitoring.

The Modbus protocol identifies two temperature-related sources.

CH2 — Thermistor Monitoring

Channel 2 provides:

  • Thermistor status
  • Thermistor alarm threshold
  • Actual measured value

ANWETECH AS05 MODBUS (1)

The holding register configuration specifies a default thermistor alarm threshold of 90°C, with a configurable range of 60°C to 110°C. ANWETECH AS05 MODBUS (1)

CH3 — Temperature/Humidity Sensor Temperature

Channel 3 monitors the temperature value from the temperature/humidity sensing element.

The SCADA or PLC can read:

  • Operating status
  • Alarm setpoint
  • Actual temperature value

ANWETECH AS05 MODBUS (1)

The corresponding alarm setting is documented with a default value of 90°C and a configurable range of 55°C to 110°C through the Modbus holding registers. ANWETECH AS05 MODBUS (1)

This provides an additional temperature reference alongside pyrolysis particle detection.


4. Humidity Monitoring Inside the Electrical Cabinet

Humidity is another parameter available through the AT-AS05 Modbus interface.

Channel 4 provides:

  • Humidity status
  • Humidity alarm setpoint
  • Actual humidity value

ANWETECH AS05 MODBUS (1)

The Modbus configuration specifies a default humidity alarm threshold of 90%, with a configurable range of 45% to 90%. ANWETECH AS05 MODBUS (1)

Humidity monitoring can therefore be included in a centralized cabinet monitoring screen together with pyrolysis particle and temperature information.

For industrial electrical installations, this gives operators a broader view of conditions inside the protected enclosure rather than relying only on a simple alarm/no-alarm signal.


5. RS485 Modbus RTU Communication

A major feature of AT-AS05 is its support for Modbus RTU over RS485.

The communication protocol specifies:

  • Protocol: Modbus RTU
  • Default baud rate: 9600 bps
  • Data bits: 8
  • Parity: None
  • Stop bit: 1
  • Device address range: 1–247
  • Maximum detector nodes on one bus: 247

ANWETECH AS05 MODBUS (1)

This makes AT-AS05 suitable for multi-detector monitoring systems.

Instead of running an individual alarm cable from every detector to a central monitoring location, multiple detectors can be installed on an RS485 bus and assigned individual addresses.

A typical architecture can be:

AT-AS05 Detector 01
AT-AS05 Detector 02
AT-AS05 Detector 03

↓

RS485 Modbus RTU Bus

↓

PLC / Industrial Controller / Modbus Gateway

↓

SCADA Monitoring System

The detector operates as a Modbus slave device. The host controller or third-party acquisition terminal actively polls detector addresses and receives the corresponding data. The protocol also allows the host system to determine that a detector is offline when it fails to respond for a configurable number of polling cycles. 


6. What Data Can SCADA Read from AT-AS05?

When integrated through a compatible Modbus master, PLC or gateway, a SCADA system can obtain significantly more information than a conventional relay-only connection.

Typical available information includes:

Monitoring Item Available through Modbus
Pyrolysis particle status Yes
Pyrolysis particle measured value Yes
Pyrolysis particle alarm setpoint Yes
Contamination level Yes
Thermistor status Yes
Thermistor measured value Yes
Temperature status Yes
Temperature measured value Yes
Temperature alarm setpoint Yes
Humidity status Yes
Humidity measured value Yes
Humidity alarm setpoint Yes
Detector fault status Yes
Detector initialization status Yes

The protocol defines the detector operating condition as well as individual channel alarm and fault status bits. ANWETECH AS05 MODBUS (1)

A SCADA interface could therefore present information such as:

Electrical Cabinet No. 12

Pyrolysis Particle: Normal
Particle Value: 320
Particle Alarm Setpoint: 500

Thermistor Temperature: 68°C
Temperature Status: Normal

Cabinet Temperature: 39°C
Humidity: 63% RH

Detector Status: Online
Detector Fault: Normal

The exact SCADA screen design depends on the PLC, gateway and SCADA software used in the project.


7. Alarm Threshold Configuration Through Modbus

AT-AS05 supports both reading and writing of holding registers.

The protocol supports:

  • 0x03 — Read Holding Registers
  • 0x06 — Write Single Holding Register

ANWETECH AS05 MODBUS (1)

Configurable parameters documented in the protocol include:

  • Detector slave address
  • Baud rate
  • Pyrolysis particle alarm setpoint
  • Thermistor alarm setpoint
  • Temperature alarm setpoint
  • Humidity alarm setpoint
  • Individual channel enable/disable status

ANWETECH AS05 MODBUS (1)

This means a compatible PLC or supervisory system can do more than simply monitor an alarm.

Depending on the system design and user permissions, selected detector settings can also be managed through Modbus communication.


8. Remote Reset and Self-Test

AT-AS05 also provides Modbus coil commands for remote detector operations.

The protocol specifies:

  • 0x0001 — Reset
  • 0x0002 — Self-Test
  • 0x0003 — Silence, listed as a reserved function

ANWETECH AS05 MODBUS (1)

A broadcast address of 0x00 can also be used for commands intended for all detectors connected to the bus.

For large installations, this can simplify detector commissioning and maintenance because selected operations can be initiated from the supervisory side rather than individually accessing each detector.


9. Relay Outputs Are Still Available

Modbus integration does not eliminate the possibility of conventional hardwired alarm integration.

AT-AS05 also provides separate relay contacts for:

  • Fire alarm
  • Fault

The product documentation specifies relay ratings of 3 A @ 30 VDC, with normally open and normally closed contact options. 3f9ba5c7-ddce-450d-8426-30baf30…

Therefore, the detector can support two different integration philosophies.

Digital Monitoring

AT-AS05 → RS485 Modbus RTU → PLC / SCADA

This approach is suitable when real-time values, individual detector addresses and parameter monitoring are required.

Hardwired Status Monitoring

AT-AS05 Relay → PLC Digital Input / Fire Alarm Input Module

This approach can be used when only alarm and fault status signals are required.

In some industrial designs, both methods may be used according to the project's control philosophy.

Each AT-AS05 detector can be assigned an individual Modbus address between 1 and 247, allowing the supervisory system to identify which cabinet is reporting abnormal conditions. ANWETECH AS05 MODBUS (1)

This type of architecture is particularly useful when many electrical cabinets need to be monitored from one control room.


11. Typical Applications

The AT-AS05 manual identifies applications including:

  • Electrical distribution rooms
  • Equipment rooms
  • Substations
  • Low-voltage and high-voltage switchgear
  • Electrical switch cabinets
  • Server cabinets
  • Generator cabinets
  • Energy storage cabinets
  • Battery compartments
  • Charging equipment
  • Prefabricated electrical cabins
  • Box-type substations
  • These are applications where localized electrical overheating can develop inside enclosed equipment and where centralized monitoring may be required.
    For industrial facilities already using PLC or SCADA infrastructure, Modbus RTU communication provides a practical method of incorporating AT-AS05 detector information into the existing supervisory system.

12. Why Combine Pyrolysis Particle, Temperature and Humidity Monitoring?

Electrical cabinet fire risk cannot always be represented by a single parameter.

Temperature provides information about thermal conditions.

Humidity provides environmental information inside the enclosure.

Pyrolysis particle detection focuses on particles generated when electrical materials begin to thermally decompose.

By combining these monitored parameters with digital communication, AT-AS05 can provide both early warning information and electrical cabinet condition data to an upper-level monitoring platform.

This allows operators to move from a simple:

Alarm / No Alarm

approach toward:

Measurement → Status Monitoring → Alarm → Centralized Response