Categories

How to Connect a Repeater Panel to an Addressable Fire Alarm Control Panel

Learn how to connect a fire alarm repeater panel to an addressable fire alarm control panel using 24VDC power and CAN bus communication.
How to Connect a Repeater Panel to an Addressable Fire Alarm Control Panel
Case Details

How to Connect AT-FR101 Repeater Panel to AT-F102 Fire Alarm Control Panel

This article explains how to connect the ANWETECH AT-FR101 Repeater Panel to the AT-F102 Addressable Fire Alarm Control Panel.

The purpose of this article is not to explain the full function of a repeater panel. It focuses only on the practical connection points that installers usually ask about:

Where does the repeater panel get power?

Does the repeater panel connect to the addressable loop?

How should CAN H and CAN L be connected?

Where should the 120-ohm terminal resistor be installed?

How many panels can be connected in the CAN network?

What should be checked if communication is abnormal?

Important Note: AT-FR101 Does Not Connect to the Addressable Loop

The AT-FR101 repeater panel should not be connected to the detector loop of the AT-F102 panel.

The addressable loop is used for field devices such as detectors, manual call points, modules, and addressable sounders. The repeater panel is not a loop device.

The AT-FR101 connects to the AT-F102 through the panel networking communication interface, normally using CAN bus communication.

This is the most important point for installation:

AT-FR101 is connected through CAN networking, not through the addressable loop.

Basic Wiring Structure

For a standard CAN bus connection between AT-FR101 and AT-F102, two parts are required:

24VDC power supply

CAN bus communication wiring

The basic wiring structure is:

AT-F102 AUX 24V or external 24VDC power supply to AT-FR101 power input

AT-F102 CAN H to AT-FR101 CAN H

AT-F102 CAN L to AT-FR101 CAN L

The 24VDC power supplies the repeater panel. The CAN H and CAN L wires provide communication between the repeater panel and the fire alarm control panel.

Step 1: Connect the 24VDC Power Supply

The AT-FR101 requires DC power input. It can be powered by the AUX 24V output of the fire alarm control panel or by an independent external 24VDC power supply.

When wiring the power supply, polarity must be correct:

24VDC positive to AT-FR101 power positive

24VDC negative to AT-FR101 power negative

Before powering on the system, check the voltage and polarity with a meter. Incorrect polarity or unstable power supply may cause the repeater panel to fail to start or operate incorrectly.

For short-distance installation, the AUX 24V output from the AT-F102 may be used if the project design allows it. For long-distance installation, the installer should consider voltage drop and may use a local independent 24VDC power supply when required.

Step 2: Connect the CAN Bus Communication Line

The AT-FR101 communicates with the AT-F102 through CAN bus networking.

The basic CAN wiring is:

AT-F102 CAN H → AT-FR101 CAN H

AT-F102 CAN L → AT-FR101 CAN L

CAN H and CAN L should not be reversed. If the two wires are reversed, communication may fail or become unstable.

The CAN bus cable should be installed according to good fire alarm system wiring practice. Keep the communication cable away from strong interference sources where possible.

Step 3: Install 120-Ohm Terminal Resistors

When using CAN bus networking, 120-ohm terminal resistors are required at the beginning and end of the CAN network.

If the system only has one AT-F102 panel and one AT-FR101 repeater panel, these two devices are normally the two ends of the CAN bus. In this case, one 120-ohm terminal resistor should be installed at the AT-F102 end, and one 120-ohm terminal resistor should be installed at the AT-FR101 end.

If there are multiple fire alarm panels or repeater panels on the same CAN bus, the resistors should only be installed at the two physical ends of the bus network.

Do not install 120-ohm resistors on every device in the middle of the CAN bus. Incorrect resistor placement may cause communication problems.

Step 4: Set the Same CAN Communication Rate

The CAN communication rate of the AT-F102 and AT-FR101 must be the same.

If the communication rate settings are different, the repeater panel and the fire alarm control panel may not communicate normally.

The AT-FR101 supports selectable CAN communication rates such as 10K, 20K, 50K, and 100Kbps. The final setting should follow the project design and communication distance.

For longer communication distance, a lower communication rate is normally more suitable for stable operation.

Step 5: Check CAN Communication Distance

The CAN communication distance of the AT-FR101 can support up to 1000 m under proper system conditions.

For long-distance wiring, installers should pay attention to:

Cable quality

Correct CAN polarity

Correct terminal resistor position

Matching communication rate

Possible voltage drop if power is supplied from the main panel

Strong electromagnetic interference near the cable route

If the repeater panel is installed far away from the AT-F102 panel, communication settings and power supply design should be checked carefully before commissioning.

Step 6: Confirm Network Node Quantity

In CAN bus networking, the total number of fire alarm control panels and repeater panels in the network can support up to 32 nodes.

The same fire alarm control panel can register multiple repeater panels. However, the same repeater panel can only register one fire alarm control panel.

This means one AT-F102 can be used with more than one AT-FR101 repeater panel, depending on the project configuration. But one AT-FR101 should not be registered to multiple fire alarm control panels at the same time.

Step 7: Register and Configure the Repeater Panel

After the wiring is completed, the AT-FR101 must be configured and registered with the fire alarm control panel according to the system commissioning procedure.

The installer should check:

The repeater panel network setting

The FACP network setting

The communication rate

The panel registration status

The system date and time

The event display status

The user authority for control functions

After registration is successful, the repeater panel should be able to display fire alarm, fault, and system event information from the registered AT-F102 panel.

Ethernet Networking Option

The AT-FR101 also supports Ethernet networking when both the fire alarm control panel and the repeater panel are equipped with Ethernet networking cards.

Ethernet networking is different from standard CAN bus wiring and requires the correct Ethernet networking module and proper network configuration.

For most simple AT-F102 to AT-FR101 repeater applications, CAN bus is usually the more direct wiring method. Ethernet can be considered when the project requires a larger network structure.

Common Wiring Mistakes

When connecting the AT-FR101 to the AT-F102, avoid these common mistakes:

Connecting the repeater panel to the addressable loop

Reversing CAN H and CAN L

Forgetting the 120-ohm terminal resistors

Installing terminal resistors at the wrong positions

Using different CAN communication rates

Using unstable or incorrect 24VDC power supply

Ignoring voltage drop on long-distance power wiring

Trying to register one repeater panel to multiple FACPs

Using Ethernet networking without the required Ethernet networking cards

These mistakes are common causes of communication failure during commissioning.

Commissioning Checklist

Before handing over the system, the installer should check the following items:

AT-FR101 powers on normally

24VDC polarity is correct

CAN H is connected to CAN H

CAN L is connected to CAN L

120-ohm terminal resistors are installed only at both ends of the CAN bus

AT-F102 and AT-FR101 use the same CAN communication rate

Communication status is normal

Repeater panel registration is completed

Fire alarm event display is tested

Fault event display is tested

Mute, sounder silence, evacuation, and reset functions are tested according to user authority

If all items are confirmed, the repeater panel can be used for remote indication and control of the AT-F102 fire alarm system.