• H208 High-Temperature Fixed Heat Detector with Customizable 70°C/80°C/90°C Alarm Thresholds and NO/NC Relay Output
  • H208 High-Temperature Fixed Heat Detector with Customizable 70°C/80°C/90°C Alarm Thresholds and NO/NC Relay Output

H208 High-Temperature Fixed Heat Detector with Customizable 70°C/80°C/90°C Alarm Thresholds and NO/NC Relay Output

No.AT-H208
The ANWETECH AT-H208 is a non-addressable, high-temperature fixed heat detector featuring a factory-default 70°C alarm threshold and customizable 80°C and 90°C alarm temperature options.
Designed for fixed-temperature fire detection, it features a DC 9–35V power supply, selectable NO/NC relay output, automatic or power-off reset options, and LED status indication.
With an operating temperature range of -40°C to +85°C, the AT-H208 is suitable for heat detection applications, including environments where dust or high airflow may make smoke detection less suitable.
  • H208 High-Temperature Fixed Heat Detector with Customizable 70°C/80°C/90°C Alarm Thresholds and NO/NC Relay Output

Description

Product Overview

High-Temperature Fixed Heat Detection with Customizable Alarm Thresholds

The ANWETECH AT-H208 High-Temperature Fixed Heat Detector provides fixed-temperature fire detection using a thermal sensing element.

The detector is supplied with a standard alarm temperature of 70°C, while alternative alarm thresholds of 80°C and 90°C are available for customization.

When the detected temperature reaches the preset alarm threshold, the detector activates its alarm indication and changes the state of its relay output.

Customizable Temperature Options

The AT-H208 offers multiple fixed-temperature alarm options to accommodate different detection temperature requirements.

  • 70°C: Factory-default alarm threshold

  • 80°C: Customizable alarm threshold

  • 90°C: Customizable alarm threshold

Alarm temperature options are specified according to the required detector configuration.

Non-Addressable Detection with Relay Output

The AT-H208 is a non-addressable heat detector with a selectable normally open (NO) or normally closed (NC) relay contact output.

The relay output enables connection to compatible fire alarm control panels or other alarm monitoring equipment.

Stable Detection Performance

The detector incorporates microcontroller-based logic, SMT electronic construction and metal shielding for resistance to electromagnetic interference.

It also supports selectable automatic reset or power-off reset modes.

7. Key Features

  • Customizable Alarm Temperature: Factory-default 70°C, with 80°C and 90°C customization options

  • High-Temperature Fixed Heat Detection: Activates an alarm when the preset temperature threshold is reached

  • Non-Addressable Design: Suitable for compatible non-addressable alarm monitoring arrangements

  • NO/NC Relay Output: Selectable normally open or normally closed alarm contacts

  • Wide Operating Voltage: DC 9–35V

  • Operating Temperature: -40°C to +85°C

  • Selectable Reset Modes: Automatic reset or power-off reset

  • LED Status Indication: Flashing green LED during normal monitoring and red LED alarm indication

  • Microcontroller-Based Logic: Designed to filter unwanted alarm signals

  • RF Interference Immunity: 10 MHz–1 GHz, 30 V/m

  • SMT Construction: Electronic manufacturing technology for operating stability

  • Positioning Mounting Base: Designed for straightforward detector installation

  • Installation Altitude: Up to 5,000 m

Technical Specifications

Parameter Specification
Brand ANWETECH
Model AT-H208
Product Type High-Temperature Fixed Heat Detector
Detection Method Fixed Temperature
Addressing Type Non-Addressable
Operating Voltage DC 9–35V
Standby Current 2 mA
Alarm Current 25 mA
Default Alarm Temperature 70°C
Customizable Alarm Temperatures 80°C, 90°C
Heat Detection Classes A1S, A2S, BS
Operating Temperature -40°C to +85°C
Relative Humidity Max. 95% RH, Non-Condensing
Normal Status Indication Flashing Green LED
Alarm Indication Red LED
Alarm Output NO/NC Relay Contact
Relay Contact Rating 5A @ DC 28V / AC 220V
Reset Mode Automatic Reset / Power-Off Reset
RF Interference Immunity 10 MHz–1 GHz, 30 V/m
Dielectric Withstand Voltage AC 3.5 kV
ESD Immunity – Air Discharge 15 kV
ESD Immunity – Contact Discharge 8 kV
Electrical Fast Transient 4 kV
Detector Dimensions Ø104 × H53 mm
Installation Altitude Up to 5,000 m
Standards Stated in Original Manual EN54-5, 

Performance, Wiring & Applications

Fixed-Temperature Detection Principle

The AT-H208 continuously monitors the surrounding temperature through its thermal sensing element.

During normal operation, the green status LED flashes.

When the surrounding temperature reaches the preset alarm threshold, the detector activates its red alarm indicator and switches its relay contact output.

The detector supports selectable reset modes according to the installation requirements.

 Customizable Alarm Temperature

The AT-H208 is available with the following fixed-temperature alarm configurations:

Alarm Temperature Configuration
70°C Factory Default
80°C Customizable
90°C Customizable

The selected alarm threshold is determined by the detector configuration. The operating temperature specification is -40°C to +85°C.

 Relay Output and Wiring Connections

The detector uses a four-terminal mounting base for power and relay connections.

Terminal Function
1 DC Power Positive (+)
2 DC Power Negative (−)
3 Relay Common (COM)
4 Normally Open / Normally Closed (NO/NC)

The required relay output mode and reset mode are selected using the jumper settings on the detector mounting base.

Reference Protection Area

The original technical manual provides the following reference protection areas based on installation height.

Installation Height Reference Protection Area
Below 6 m 60 m² per Detector
6–12 m 80 m² per Detector

 Installation

  • Select a suitable mounting position, generally near the center of the protected ceiling area.

  • Open the small cover on the mounting base to access the jumper settings.

  • Configure the required reset and alarm output modes.

  • Connect the power supply and relay signal wiring to the corresponding terminals.

  • Secure the mounting base to the ceiling using screws.

  • Align the detector positioning features with the mounting base and rotate clockwise to secure the detector.



Installation The AT-H208 can be used for fixed-temperature heat detection in environments where smoke detection may be less suitable, including:

  • High-airflow environments

  • Dusty environments

  • Locations requiring fixed-temperature fire detection

 Functional Testing

The original manual describes a simulated heat alarm test using a hair dryer or another heating device positioned approximately 50 cm from the detector.

Heat is directed toward the thermal sensing element until the detector reaches its preset alarm condition.

When activated, the detector displays its alarm indication and sends an alarm signal through its output connection.

 Installation Precautions

  • Avoid installation in areas exposed to direct sunlight or unwanted heat sources.

  • Ensure that the detector base is securely mounted.

  • Check that the wiring connections are reliable.

  • Maintain the detector's power supply during normal operation.

  • Perform a simulated fire alarm test approximately every six months to check detector operation.