The ANWETECH AT-H208 High-Temperature Fixed Heat Detector provides fixed-temperature fire detection using a thermal sensing element.
The detector is supplied with a standard alarm temperature of 70°C, while alternative alarm thresholds of 80°C and 90°C are available for customization.
When the detected temperature reaches the preset alarm threshold, the detector activates its alarm indication and changes the state of its relay output.
The AT-H208 offers multiple fixed-temperature alarm options to accommodate different detection temperature requirements.
70°C: Factory-default alarm threshold
80°C: Customizable alarm threshold
90°C: Customizable alarm threshold
Alarm temperature options are specified according to the required detector configuration.
The AT-H208 is a non-addressable heat detector with a selectable normally open (NO) or normally closed (NC) relay contact output.
The relay output enables connection to compatible fire alarm control panels or other alarm monitoring equipment.
The detector incorporates microcontroller-based logic, SMT electronic construction and metal shielding for resistance to electromagnetic interference.
It also supports selectable automatic reset or power-off reset modes.
Customizable Alarm Temperature: Factory-default 70°C, with 80°C and 90°C customization options
High-Temperature Fixed Heat Detection: Activates an alarm when the preset temperature threshold is reached
Non-Addressable Design: Suitable for compatible non-addressable alarm monitoring arrangements
NO/NC Relay Output: Selectable normally open or normally closed alarm contacts
Wide Operating Voltage: DC 9–35V
Operating Temperature: -40°C to +85°C
Selectable Reset Modes: Automatic reset or power-off reset
LED Status Indication: Flashing green LED during normal monitoring and red LED alarm indication
Microcontroller-Based Logic: Designed to filter unwanted alarm signals
RF Interference Immunity: 10 MHz–1 GHz, 30 V/m
SMT Construction: Electronic manufacturing technology for operating stability
Positioning Mounting Base: Designed for straightforward detector installation
Installation Altitude: Up to 5,000 m
| Parameter | Specification |
|---|---|
| Brand | ANWETECH |
| Model | AT-H208 |
| Product Type | High-Temperature Fixed Heat Detector |
| Detection Method | Fixed Temperature |
| Addressing Type | Non-Addressable |
| Operating Voltage | DC 9–35V |
| Standby Current | 2 mA |
| Alarm Current | 25 mA |
| Default Alarm Temperature | 70°C |
| Customizable Alarm Temperatures | 80°C, 90°C |
| Heat Detection Classes | A1S, A2S, BS |
| Operating Temperature | -40°C to +85°C |
| Relative Humidity | Max. 95% RH, Non-Condensing |
| Normal Status Indication | Flashing Green LED |
| Alarm Indication | Red LED |
| Alarm Output | NO/NC Relay Contact |
| Relay Contact Rating | 5A @ DC 28V / AC 220V |
| Reset Mode | Automatic Reset / Power-Off Reset |
| RF Interference Immunity | 10 MHz–1 GHz, 30 V/m |
| Dielectric Withstand Voltage | AC 3.5 kV |
| ESD Immunity – Air Discharge | 15 kV |
| ESD Immunity – Contact Discharge | 8 kV |
| Electrical Fast Transient | 4 kV |
| Detector Dimensions | Ø104 × H53 mm |
| Installation Altitude | Up to 5,000 m |
| Standards Stated in Original Manual | EN54-5, |
The AT-H208 continuously monitors the surrounding temperature through its thermal sensing element.
During normal operation, the green status LED flashes.
When the surrounding temperature reaches the preset alarm threshold, the detector activates its red alarm indicator and switches its relay contact output.
The detector supports selectable reset modes according to the installation requirements.
The AT-H208 is available with the following fixed-temperature alarm configurations:
| Alarm Temperature | Configuration |
|---|---|
| 70°C | Factory Default |
| 80°C | Customizable |
| 90°C | Customizable |
The selected alarm threshold is determined by the detector configuration. The operating temperature specification is -40°C to +85°C.
The detector uses a four-terminal mounting base for power and relay connections.
| Terminal | Function |
|---|---|
| 1 | DC Power Positive (+) |
| 2 | DC Power Negative (−) |
| 3 | Relay Common (COM) |
| 4 | Normally Open / Normally Closed (NO/NC) |
The required relay output mode and reset mode are selected using the jumper settings on the detector mounting base.
The original technical manual provides the following reference protection areas based on installation height.
| Installation Height | Reference Protection Area |
|---|---|
| Below 6 m | 60 m² per Detector |
| 6–12 m | 80 m² per Detector |
Select a suitable mounting position, generally near the center of the protected ceiling area.
Open the small cover on the mounting base to access the jumper settings.
Configure the required reset and alarm output modes.
Connect the power supply and relay signal wiring to the corresponding terminals.
Secure the mounting base to the ceiling using screws.
Align the detector positioning features with the mounting base and rotate clockwise to secure the detector.
High-airflow environments
Dusty environments
Locations requiring fixed-temperature fire detection
The original manual describes a simulated heat alarm test using a hair dryer or another heating device positioned approximately 50 cm from the detector.
Heat is directed toward the thermal sensing element until the detector reaches its preset alarm condition.
When activated, the detector displays its alarm indication and sends an alarm signal through its output connection.
Avoid installation in areas exposed to direct sunlight or unwanted heat sources.
Ensure that the detector base is securely mounted.
Check that the wiring connections are reliable.
Maintain the detector's power supply during normal operation.
Perform a simulated fire alarm test approximately every six months to check detector operation.