UV/IR flame detectors are widely used in industrial locations where fires may develop rapidly and conventional smoke detection may not provide sufficiently fast warning. Typical applications include oil and gas facilities, fuel storage areas, petrochemical plants, power generation facilities and other locations containing flammable materials.
However, testing a flame detector with a real flame may create unnecessary safety risks, especially in hazardous or explosion-risk environments.
A portable flame simulator provides an alternative method. It produces optical radiation designed to simulate characteristics associated with a real flame, allowing technicians to perform a functional detector test without igniting fuel or creating an open flame.
The ANWETECH AT-FD-T01 Explosion-Proof Flame Simulator simultaneously produces infrared and ultraviolet radiation. According to the product documentation, it can simulate a real flame under open-flame-free conditions and is intended for routine functional testing and maintenance of flame detectors.
Testing with a real flame may introduce several practical and safety concerns:
A flame simulator allows the test to be carried out without directly producing a fire at the detector location.
It is important to understand that a flame simulator is mainly used for a functional response test. It does not replace every inspection, calibration or commissioning procedure specified by the flame detector manufacturer or the project fire protection design.
The AT-FD-T01 uses an electric-arc light source to generate both infrared and ultraviolet radiation.
When the device is directed toward a compatible flame detector, the emitted optical energy simulates the radiation characteristics associated with a fire. The detector processes this signal through its internal sensing and alarm algorithm.
When the received signal satisfies the detector’s alarm criteria, the detector may:
The actual detector response depends on its sensing technology, programmed sensitivity, viewing angle, optical condition and manufacturer-specific alarm algorithm.
The product documentation confirms infrared and ultraviolet output, but it does not specify exact emitted wavelength bands or a universal detector compatibility list. Therefore, compatibility should be confirmed before testing a specific detector model.
The following procedure is a general engineering guide. The detector manufacturer’s instructions, project cause-and-effect matrix and site safety procedure must take priority.
Before starting the test, record:
| Required Information | Example |
|---|---|
| Detector manufacturer | To be confirmed |
| Detector model | To be confirmed |
| Detection technology | UV, IR, UV/IR, IR2 or IR3 |
| Installed location | Process area, tank area, transformer room, etc. |
| Detector address or zone | According to the fire alarm system |
| Connected control outputs | Alarm, shutdown, deluge, foam or gas suppression |
Do not assume that one flame simulator will automatically operate every UV, IR, UV/IR, IR2 or IR3 detector. Detector compatibility depends on optical wavelength, signal modulation and alarm-processing logic.
Before activating the flame simulator, determine what will happen when the detector enters alarm.
A flame detector alarm may initiate:
Where automatic release or shutdown functions are connected, the system must be placed in the approved test condition by authorized personnel.
Do not isolate safety functions without following the site permit and impairment-control procedure.
Notify the responsible personnel before starting.
Confirm:
This prevents the test alarm from being treated as an actual emergency.
Check the flame detector before using the simulator.
Inspect:
A dirty optical window can reduce the amount of simulated radiation reaching the detector.
The flame simulator should not be used to hide an installation or maintenance problem. Physical inspection and functional testing should be completed together.
Before the test, confirm that the simulator:
The confirmed electrical information for the AT-FD-T01 is:
| Electrical Parameter | Confirmed Value |
|---|---|
| Operating voltage | 12 V DC |
| Operating current | ≤3 A |
| Working time | Approximately 60 minutes |
| Charging voltage | 16.8 V DC |
| Charging current | 1 A |
| Charging time | Approximately 4 hours |
These values are taken from the supplied product documentation.
Stand within the permitted operating distance and point the simulator directly toward the detector’s optical sensing window.
The AT-FD-T01 product documentation specifies an operating distance of:
≤8 m
For the best test condition:
The maximum achievable test distance may be affected by detector sensitivity, alignment, lens contamination, ambient light, weather and the detector manufacturer’s alarm algorithm.
Therefore, the stated 8 m should not be interpreted as a guaranteed response distance for every detector model or every site condition.
Operate the AT-FD-T01 according to its approved operating method while keeping it directed toward the detector.
Observe:
Do not continue exposing the detector longer than necessary after the alarm has been confirmed.
The source document does not specify a fixed detector response time. Therefore, no universal alarm time should be stated for this product.
A successful functional test should not only confirm that the detector LED operates.
The technician should verify the entire required signal path:
Flame simulator → Flame detector → Fire alarm control panel → Required alarm or control output
For example, verify whether:
A detector that indicates locally but does not transmit an alarm to the control panel may have a wiring, programming, module or communication problem.
After confirming the alarm:
The system must not be left with disabled outputs or isolated suppression equipment.
A functional test record should include:
| Test Record Item | Information to Record |
|---|---|
| Test date | Date and time |
| Detector model | Manufacturer and model |
| Detector location | Area or equipment protected |
| Detector address | Loop, address or zone |
| Test device | ANWETECH AT-FD-T01 |
| Test distance | Actual distance used |
| Detector response | Pass or fail |
| Panel response | Pass or fail |
| Output response | Pass, fail or isolated |
| Technician | Name and signature |
| Remarks | Cleaning, fault or corrective action |
Documenting the actual test distance is useful for future maintenance comparisons.
The following information is confirmed in the corresponding product documentation.
| Category | Parameter | Confirmed Specification |
|---|---|---|
| Key performance | Optical output | Infrared and ultraviolet |
| Key performance | Operating distance | ≤8 m |
| Protection | Explosion-proof marking | Ex db IIC T4 Gb / Ex tb IIIC T135°C Db |
| Protection | Ingress protection | IP65 |
| Electrical | Operating voltage | 12 V DC |
| Electrical | Operating current | ≤3 A |
| Electrical | Working time | Approximately 60 minutes |
| Charging | Charging voltage | 16.8 V DC |
| Charging | Charging current | 1 A |
| Charging | Charging time | Approximately 4 hours |
| Environment | Operating temperature | −20°C to +60°C |
| Environment | Operating humidity | 10–90% RH, non-condensing |
| Environment | Charging and storage temperature | 0°C to +45°C |
| Mechanical | Housing material | Aluminium alloy |
| Mechanical | Weight | Approximately 2.0 kg |
| Dimensions | Overall size shown in drawing | Approximately 210 × 117 × 79 mm |
Based on its intended function, the AT-FD-T01 can support flame detector inspection and maintenance in industrial locations such as:
Final suitability depends on the project’s hazardous-area classification, required certification, environmental conditions and the installed detector model.
Before supplying or using the AT-FD-T01, request the following detector information:
The AT-FD-T01 documentation confirms simultaneous UV and IR output, but it does not confirm compatibility with every detector brand or every UV/IR, IR2 or IR3 detection algorithm.
For project enquiries, customers should provide the detector datasheet or detector model before compatibility is confirmed.
Possible reasons include:
Move closer, clean the detector lens, confirm detector status and check model compatibility before concluding that the detector is defective.
Check:
Check whether:
Yes. The product documentation states that the device outputs infrared and ultraviolet radiation to simulate a real flame without using an open flame.
The documented operating distance is no more than 8 m. Actual response distance depends on detector model, alignment, sensitivity and environmental conditions.
Universal compatibility is not confirmed in the supplied documentation. The detector brand, model, sensing wavelengths and manufacturer requirements should be checked before testing.
The supplied documentation lists the explosion-protection marking as Ex db IIC T4 Gb / Ex tb IIIC T135°C Db. Project acceptance should be based on the actual certificate and the site’s required hazardous-area standard.
The documented ingress-protection rating is IP65.
The documented working time is approximately 60 minutes under the specified operating conditions.
The documented charging time is approximately four hours, using 16.8 V DC at 1 A.
This depends on the approved test procedure. Where testing could initiate gas, foam, deluge or equipment shutdown, authorized personnel should place the relevant outputs in a controlled test condition before starting. All isolated functions must be restored immediately after the test.