How to Test UV/IR Flame Detectors Without an Open Flame

Learn how to test UV/IR flame detectors without an open flame using the AT-FD-T01 explosion-proof flame simulator, with up to 8 m operating distance and portable battery-powered operation.
How to Test UV/IR Flame Detectors Without an Open Flame
Case Details

How to Test UV/IR Flame Detectors Without an Open Flame

Introduction

UV/IR flame detectors are widely used in industrial locations where fires may develop rapidly and conventional smoke detection may not provide sufficiently fast warning. Typical applications include oil and gas facilities, fuel storage areas, petrochemical plants, power generation facilities and other locations containing flammable materials.

However, testing a flame detector with a real flame may create unnecessary safety risks, especially in hazardous or explosion-risk environments.

A portable flame simulator provides an alternative method. It produces optical radiation designed to simulate characteristics associated with a real flame, allowing technicians to perform a functional detector test without igniting fuel or creating an open flame.

The ANWETECH AT-FD-T01 Explosion-Proof Flame Simulator simultaneously produces infrared and ultraviolet radiation. According to the product documentation, it can simulate a real flame under open-flame-free conditions and is intended for routine functional testing and maintenance of flame detectors.


Why Test a Flame Detector Without an Open Flame?

Testing with a real flame may introduce several practical and safety concerns:

  • Ignition risks in areas containing flammable gas, vapour or combustible dust
  • Difficulty controlling flame size and radiation output
  • Restrictions on hot work and open-flame activities
  • Possible interference from wind or environmental conditions
  • Additional site permits and fire-watch requirements
  • Risk of accidentally activating connected suppression equipment

A flame simulator allows the test to be carried out without directly producing a fire at the detector location.

It is important to understand that a flame simulator is mainly used for a functional response test. It does not replace every inspection, calibration or commissioning procedure specified by the flame detector manufacturer or the project fire protection design.


How the AT-FD-T01 Flame Simulator Works

The AT-FD-T01 uses an electric-arc light source to generate both infrared and ultraviolet radiation.

When the device is directed toward a compatible flame detector, the emitted optical energy simulates the radiation characteristics associated with a fire. The detector processes this signal through its internal sensing and alarm algorithm.

When the received signal satisfies the detector’s alarm criteria, the detector may:

  • Illuminate its alarm indicator
  • Transmit an alarm signal to the fire alarm control panel
  • Change its relay output state
  • Activate programmed warning or suppression sequences

The actual detector response depends on its sensing technology, programmed sensitivity, viewing angle, optical condition and manufacturer-specific alarm algorithm.

The product documentation confirms infrared and ultraviolet output, but it does not specify exact emitted wavelength bands or a universal detector compatibility list. Therefore, compatibility should be confirmed before testing a specific detector model.


Recommended UV/IR Flame Detector Testing Procedure

The following procedure is a general engineering guide. The detector manufacturer’s instructions, project cause-and-effect matrix and site safety procedure must take priority.

Step 1: Identify the Flame Detector

Before starting the test, record:

Required Information Example
Detector manufacturer To be confirmed
Detector model To be confirmed
Detection technology UV, IR, UV/IR, IR2 or IR3
Installed location Process area, tank area, transformer room, etc.
Detector address or zone According to the fire alarm system
Connected control outputs Alarm, shutdown, deluge, foam or gas suppression

Do not assume that one flame simulator will automatically operate every UV, IR, UV/IR, IR2 or IR3 detector. Detector compatibility depends on optical wavelength, signal modulation and alarm-processing logic.


Step 2: Review the Cause-and-Effect Logic

Before activating the flame simulator, determine what will happen when the detector enters alarm.

A flame detector alarm may initiate:

  • Local sounder or beacon operation
  • Fire alarm control panel alarm
  • Equipment shutdown
  • Fuel or gas valve closure
  • HVAC shutdown
  • Deluge or foam-system release
  • Gas suppression pre-discharge sequence
  • Signal transmission to a control room or BMS

Where automatic release or shutdown functions are connected, the system must be placed in the approved test condition by authorized personnel.

Do not isolate safety functions without following the site permit and impairment-control procedure.


Step 3: Inform the Control Room

Notify the responsible personnel before starting.

Confirm:

  • The detector being tested
  • The expected alarm indication
  • Whether suppression outputs are isolated
  • Whether shutdown signals are temporarily inhibited
  • Who will confirm receipt of the alarm
  • Who will restore the system after testing

This prevents the test alarm from being treated as an actual emergency.


Step 4: Inspect the Detector

Check the flame detector before using the simulator.

Inspect:

  • Detector lens cleanliness
  • Correct mounting orientation
  • Obstructions within the field of view
  • Mechanical damage
  • Cable and conduit condition
  • Power and normal-status indicators
  • Signs of water, dust, oil or contamination

A dirty optical window can reduce the amount of simulated radiation reaching the detector.

The flame simulator should not be used to hide an installation or maintenance problem. Physical inspection and functional testing should be completed together.


Step 5: Check the AT-FD-T01

Before the test, confirm that the simulator:

  • Has sufficient battery power
  • Has no visible housing damage
  • Has a clean optical output window
  • Has been charged with the correct charger
  • Is suitable for the site’s hazardous-area requirements
  • Is operated within its specified environmental conditions

The confirmed electrical information for the AT-FD-T01 is:

Electrical Parameter Confirmed Value
Operating voltage 12 V DC
Operating current ≤3 A
Working time Approximately 60 minutes
Charging voltage 16.8 V DC
Charging current 1 A
Charging time Approximately 4 hours

These values are taken from the supplied product documentation.


Step 6: Position the Simulator

Stand within the permitted operating distance and point the simulator directly toward the detector’s optical sensing window.

The AT-FD-T01 product documentation specifies an operating distance of:

≤8 m

For the best test condition:

  • Maintain a clear line of sight
  • Aim at the detector’s optical window
  • Avoid testing through glass or transparent barriers unless approved
  • Avoid excessive movement while operating the simulator
  • Begin at a practical short distance when compatibility has not previously been confirmed
  • Increase the distance only after a successful response has been verified

The maximum achievable test distance may be affected by detector sensitivity, alignment, lens contamination, ambient light, weather and the detector manufacturer’s alarm algorithm.

Therefore, the stated 8 m should not be interpreted as a guaranteed response distance for every detector model or every site condition.


Step 7: Activate the Flame Simulator

Operate the AT-FD-T01 according to its approved operating method while keeping it directed toward the detector.

Observe:

  • Detector alarm LED
  • Fire alarm control panel indication
  • Detector address or zone
  • Alarm relay status
  • Remote annunciator indication
  • BMS or control-room signal
  • Programmed warning outputs

Do not continue exposing the detector longer than necessary after the alarm has been confirmed.

The source document does not specify a fixed detector response time. Therefore, no universal alarm time should be stated for this product.


Step 8: Confirm the Complete Alarm Path

A successful functional test should not only confirm that the detector LED operates.

The technician should verify the entire required signal path:

Flame simulator → Flame detector → Fire alarm control panel → Required alarm or control output

For example, verify whether:

  • The correct detector address appears
  • The correct zone description is displayed
  • The alarm relay changes state
  • The correct sounder or beacon activates
  • The control room receives the correct signal
  • Required shutdown or release logic is confirmed under controlled test conditions

A detector that indicates locally but does not transmit an alarm to the control panel may have a wiring, programming, module or communication problem.


Step 9: Stop the Test and Reset the System

After confirming the alarm:

  1. Stop operating the flame simulator.
  2. Allow the detector to return to its normal condition.
  3. Reset the fire alarm control panel if required.
  4. Restore any isolated outputs.
  5. Confirm that all fault and disablement indications are cleared.
  6. Verify that suppression and shutdown systems have returned to normal service.
  7. Inform the control room that testing is complete.

The system must not be left with disabled outputs or isolated suppression equipment.


Step 10: Record the Test Results

A functional test record should include:

Test Record Item Information to Record
Test date Date and time
Detector model Manufacturer and model
Detector location Area or equipment protected
Detector address Loop, address or zone
Test device ANWETECH AT-FD-T01
Test distance Actual distance used
Detector response Pass or fail
Panel response Pass or fail
Output response Pass, fail or isolated
Technician Name and signature
Remarks Cleaning, fault or corrective action

Documenting the actual test distance is useful for future maintenance comparisons.


Confirmed AT-FD-T01 Technical Data

The following information is confirmed in the corresponding product documentation.

Category Parameter Confirmed Specification
Key performance Optical output Infrared and ultraviolet
Key performance Operating distance ≤8 m
Protection Explosion-proof marking Ex db IIC T4 Gb / Ex tb IIIC T135°C Db
Protection Ingress protection IP65
Electrical Operating voltage 12 V DC
Electrical Operating current ≤3 A
Electrical Working time Approximately 60 minutes
Charging Charging voltage 16.8 V DC
Charging Charging current 1 A
Charging Charging time Approximately 4 hours
Environment Operating temperature −20°C to +60°C
Environment Operating humidity 10–90% RH, non-condensing
Environment Charging and storage temperature 0°C to +45°C
Mechanical Housing material Aluminium alloy
Mechanical Weight Approximately 2.0 kg
Dimensions Overall size shown in drawing Approximately 210 × 117 × 79 mm

Where Can the AT-FD-T01 Be Used?

Based on its intended function, the AT-FD-T01 can support flame detector inspection and maintenance in industrial locations such as:

  • Oil and gas processing areas
  • Petrochemical facilities
  • Fuel storage terminals
  • Refineries
  • Chemical plants
  • Power generation facilities
  • Transformer areas
  • Warehouses containing flammable materials
  • Marine and offshore facilities
  • Industrial fire detection projects

Final suitability depends on the project’s hazardous-area classification, required certification, environmental conditions and the installed detector model.


Important Compatibility Considerations

Before supplying or using the AT-FD-T01, request the following detector information:

  1. Detector brand
  2. Detector model
  3. Detection technology
  4. UV and IR sensing wavelength
  5. Required optical test-lamp model
  6. Alarm response requirements
  7. Test distance
  8. Hazardous-area classification
  9. Required certification
  10. Detector manufacturer’s test instructions

The AT-FD-T01 documentation confirms simultaneous UV and IR output, but it does not confirm compatibility with every detector brand or every UV/IR, IR2 or IR3 detection algorithm.

For project enquiries, customers should provide the detector datasheet or detector model before compatibility is confirmed.


Common Testing Problems

The detector does not respond

Possible reasons include:

  • The simulator is not correctly aligned
  • The test distance is too great
  • The detector lens is contaminated
  • The detector is not powered
  • The detector sensitivity or delay setting is different
  • The detector requires a manufacturer-specific test signal
  • The simulator battery level is insufficient
  • The detector’s sensing technology is not compatible
  • Strong ambient optical interference is present

Move closer, clean the detector lens, confirm detector status and check model compatibility before concluding that the detector is defective.

The detector alarms, but the fire alarm panel does not

Check:

  • Detector wiring
  • Address or zone configuration
  • Interface module programming
  • Alarm relay connections
  • Control panel event log
  • Loop communication
  • Input logic and cause-and-effect programming

The panel receives the alarm, but connected equipment does not operate

Check whether:

  • The output was intentionally isolated for testing
  • Cause-and-effect programming is correct
  • Output modules are enabled
  • Control relays are correctly wired
  • External equipment has power
  • Shutdown or suppression interlocks are active

Frequently Asked Questions

Can the AT-FD-T01 test a UV/IR flame detector without producing fire?

Yes. The product documentation states that the device outputs infrared and ultraviolet radiation to simulate a real flame without using an open flame.

What is the maximum testing distance?

The documented operating distance is no more than 8 m. Actual response distance depends on detector model, alignment, sensitivity and environmental conditions.

Can it test every UV, IR, UV/IR, IR2 or IR3 detector?

Universal compatibility is not confirmed in the supplied documentation. The detector brand, model, sensing wavelengths and manufacturer requirements should be checked before testing.

Is the AT-FD-T01 explosion-proof?

The supplied documentation lists the explosion-protection marking as Ex db IIC T4 Gb / Ex tb IIIC T135°C Db. Project acceptance should be based on the actual certificate and the site’s required hazardous-area standard.

What is the ingress-protection rating?

The documented ingress-protection rating is IP65.

How long can the simulator operate?

The documented working time is approximately 60 minutes under the specified operating conditions.

How long does charging take?

The documented charging time is approximately four hours, using 16.8 V DC at 1 A.

Should automatic suppression outputs remain active during testing?

This depends on the approved test procedure. Where testing could initiate gas, foam, deluge or equipment shutdown, authorized personnel should place the relevant outputs in a controlled test condition before starting. All isolated functions must be restored immediately after the test.