Categories

Goce Delčev Library – Veles Addressable Fire Alarm Project

ANWETECH AT-F101 addressable fire alarm system installed at Goce Delčev Library in Veles, with smoke detection, manual alarms and sounder beacons.
Jul 24th,2026 143 Views


Project Overview

Goce Delčev Library in Veles, North Macedonia, is protected by an addressable fire alarm system built around the ANWETECH AT-F101 Addressable Fire Alarm Control Panel.

The installed system includes addressable smoke detectors for automatic fire detection, manual call points for occupant-initiated alarms, and sounder beacons for audible and visual warning. Together, these devices provide an integrated fire detection and alarm solution suitable for a public library environment.

The AT-F101 provides the central monitoring and control platform for the system. Its addressable architecture enables individual field devices to be identified by address, helping operators determine the source of a fire alarm or system fault more efficiently than with a non-addressable detection arrangement.

Project Information Table

Project Item Confirmed Information
Project Name Goce Delčev Library – Veles
Location Veles, North Macedonia
Application Library fire detection and alarm
System Type Addressable fire alarm system
Main Control Panel ANWETECH AT-F101 Addressable Fire Alarm Control Panel
Automatic Detection Addressable smoke detectors
Manual Alarm Devices Addressable manual call points
Alarm Notification Addressable sounder beacons
Fire Indication Capacity Up to 16 fire indication zones
Loop Configuration One addressable loop
Maximum Panel Capacity Up to 120 addressable points
Loop Wiring Class A or Class B configuration
Panel Standard EN 54-2 and EN 54-4

Project-specific device quantities, installation date and detailed area allocation are not published.

Fire Risk Analysis

Libraries require reliable fire detection because they commonly contain a considerable amount of combustible material, including books, paper records, shelving, furniture and interior finishes. A fire involving paper-based materials can develop progressively before becoming visible across a larger area.

Electrical equipment, lighting circuits, power supplies and other building services may also introduce potential ignition sources. If a fire begins in a less frequently occupied section of the building, delayed discovery could allow smoke and heat to spread before manual intervention is possible.

The principal fire-safety requirements for this application therefore include:

  • Automatic smoke detection during occupied and unoccupied periods.
  • Clear identification of the device or location reporting an alarm.
  • Manual alarm initiation for occupants who discover a fire.
  • Audible and visual notification to support an organized response.
  • Central supervision of alarms and system faults.
  • Suitable zoning and cause-and-effect programming for the building layout.

Why the AT-F101 System Was Selected

The ANWETECH AT-F101 was selected as the central fire alarm control panel because its addressable architecture is suitable for projects that require individual field-device identification and organized alarm management.

The panel supports one addressable loop with a maximum capacity of 120 addressable points. It also supports up to 16 fire indication zones, allowing connected devices to be logically organized according to the protected building layout.

For a library application, addressable identification provides an important operational benefit. When a smoke detector, manual call point or other connected device reports an event, the panel can identify the relevant address instead of presenting only a general circuit alarm. This helps building personnel investigate the affected location more efficiently.

The AT-F101 also supports Class A and Class B loop wiring, allowing the loop arrangement to be selected according to the approved project design and site requirements.

System Design Concept

The system was designed around four essential fire-alarm functions: detection, manual initiation, notification and centralized control.

Automatic smoke detection

Addressable smoke detectors provide automatic detection within the protected library environment. Each detector is assigned an individual address so that its status can be monitored by the AT-F101 panel.

Manual fire alarm initiation

Addressable manual call points allow occupants or staff to initiate a fire alarm manually after discovering smoke or fire. As addressable devices, their activation locations can be identified at the control panel.

Audible and visual notification

Addressable sounder beacons provide audible and visual alarm notification. This combination helps alert building occupants and supports evacuation or emergency response procedures.

Central monitoring and control

The AT-F101 receives information from the addressable field devices, displays fire and fault events, and manages programmed output responses. Devices can be assigned to fire indication zones based on the building’s approved alarm zoning plan.

System Configuration

The confirmed system consists of:

  • ANWETECH AT-F101 Addressable Fire Alarm Control Panel
  • Addressable smoke detectors
  • Addressable manual call points
  • Addressable sounder beacons
  • Addressable loop wiring
  • Fire indication zone programming
  • Cause-and-effect programming as required by the approved system design

The AT-F101 technical configuration provides:

  • One addressable loop
  • Up to 120 addressable points
  • Up to 16 fire indication zones
  • Class A or Class B loop wiring
  • Default, zonal and specific cause-and-effect programming
  • Address writing and reading
  • Automatic loop learning
  • Detector and device configuration
  • Fire alarm, fault and supervised output functions

Individual field-device models and installed quantities have been intentionally omitted because they were not confirmed for this project.

Installation and Commissioning

The addressable devices are connected to the AT-F101 through the fire alarm loop and assigned individual addresses according to the project’s address schedule.

The documented AT-F101 installation and commissioning workflow includes:

  1. Preparing the device address table, loop wiring diagram and cause-and-effect requirements.
  2. Assigning and verifying the address of each field device.
  3. Checking the loop wiring and panel terminations.
  4. Performing the loop-learning procedure.
  5. Configuring fire indication zones.
  6. Setting the correct device type for each connected point.
  7. Programming the required default, zonal or specific cause-and-effect logic.
  8. Testing smoke detectors, manual call points and alarm notification devices.
  9. Checking alarm indications, fault supervision and output activation.
  10. Recording the final addressing and programming information for system operation and maintenance.

The precise cable routes, device locations, test results and commissioning date for the Goce Delčev Library installation have not been published and are therefore not included.

Project Value

The addressable fire alarm system provides Goce Delčev Library with a structured method of detecting, identifying and communicating fire events.

Key project benefits include:

  • Earlier warning through automatic smoke detection.
  • Individual identification of addressable alarm devices.
  • Manual alarm initiation for library staff and occupants.
  • Audible and visual warning through sounder beacons.
  • Centralized monitoring from the AT-F101 control panel.
  • Logical organization of devices into fire indication zones.
  • Support for programmed alarm responses through cause-and-effect logic.
  • Easier fault investigation and system maintenance through addressable point identification.

This project demonstrates how a compact addressable fire alarm control panel can be combined with automatic detectors, manual call points and notification devices to form an integrated fire-safety solution for a library.

Recommended Applications

The AT-F101 addressable fire alarm system is suitable for similar small and medium-sized applications requiring individual device identification and centralized fire-alarm management, including:

  • Public and municipal libraries
  • School and university libraries
  • Archives and document storage areas
  • Educational buildings
  • Community cultural centers
  • Museums and exhibition spaces
  • Administrative buildings
  • Small public-service facilities

The final device quantities, detector spacing, zoning and cause-and-effect strategy must be determined according to the building layout, local requirements and approved fire-safet