The ANWETECH AT-AS05 Pyrolysis Particle Electrical Fire Monitoring Detector is designed for early electrical fire monitoring inside electrical cabinets and other relatively enclosed electrical equipment spaces.
It monitors pyrolysis particles and gases generated when electrical cables, insulation materials and electrical components begin to overheat. According to the product manual, the detector can provide an alarm before visible smoke is produced, helping identify abnormal heating at an early stage.
The AT-AS05 supports RS485 communication, fire alarm relay output and fault relay output, allowing integration with an upper-level monitoring system.
Electrical faults do not always begin with immediate flame or visible smoke. In many cases, electrical cables, insulation materials, switches and other electrical components first experience abnormal heating.
During this early stage, heated materials may decompose and release very small pyrolysis particles and gases.
The AT-AS05 is designed to monitor these changes and provide early warning before visible smoke develops.
The detector is specified for monitoring particles and gases generated by overheating of materials and electrical equipment including:
The manual states that the detector can monitor pyrolysis particles with a diameter range of approximately 1 nm to 10 nm.
This makes the AT-AS05 suitable for early electrical fire monitoring in electrical cabinets and other relatively enclosed electrical equipment environments.
The detector monitors particles and gases generated when electrical insulation materials and electrical equipment begin to overheat.
It is designed to provide warning before visible smoke appears.
The specified monitored pyrolysis-particle diameter range is:
1 nm–10 nm
This allows the detector to monitor products generated during the early overheating stage of electrical materials.
The product manual lists applications including:
It can also be used in other relatively enclosed electrical spaces specified in the manual.
The AT-AS05 supports RS485 communication with an upper-level host system.
Supported baud rates:
2400 bps, 4800 bps, 9600 bps, 19200 bps
Default baud rate:
9600 bps
Default RS485 address:
01
The detector provides a dedicated fire alarm relay:
3 A @ 30 VDC
Normally Open and Normally Closed contacts are available.
A separate fault relay is also provided:
3 A @ 30 VDC
Normally Open and Normally Closed contacts are available.
When an alarm condition is detected, the detector alarm indicator remains illuminated and the device can provide an audible alarm.
The audible alarm can be enabled or disabled through the upper-level host system.
Default temperature alarm threshold:
90°C
Adjustable range:
55°C–120°C
Rated operating voltage:
DC 24 V
Supported input range:
DC 9–36 V
| Parameter | Specification |
|---|---|
| Model | AT-AS05 |
| Product Type | Pyrolysis Particle Electrical Fire Monitoring Detector |
| Rated Operating Voltage | DC 24 V |
| Input Voltage Range | DC 9–36 V |
| Operating Current | 35 mA ± 5 mA at DC 24 V |
| Operating Humidity | ≤95% RH |
| Ambient Temperature | -30°C to +70°C |
| Pyrolysis Particle Alarm Threshold | 0–1000 pyrolysis particle units |
| Temperature Alarm Threshold | Default 90°C |
| Adjustable Temperature Range | 55°C–120°C |
| Monitored Gas | Hydrocarbon-chain compound gases associated with PVC cables and electrical equipment |
| Communication | Switching signal or RS485 |
| RS485 Communication Distance | ≤1.5 km to upper-level host |
| Fire Alarm Relay | 3 A @ 30 VDC, NO/NC selectable |
| Fault Relay | 3 A @ 30 VDC, NO/NC selectable |
| Installation | Magnetic mounting / Ceiling mounting |
| Product Dimensions | 100 × 100 × 32.2 mm |
| Electromagnetic Compatibility | According to GB16838 |
The technical specifications above are taken from the supplied product manual.
The AT-AS05 uses a standard RS485 interface for communication with an upper-level host.
Baud Rate Options:
2400 bps, 4800 bps, 9600 bps, 19200 bps
Default Baud Rate:
9600 bps
Default Address:
01
Maximum RS485 Communication Distance:
≤1.5 km to the upper-level host
Communication Protocol:
—
The supplied manual does not identify Modbus or another specific application-layer communication protocol. This should be confirmed separately before publishing any Modbus claim.
The AT-AS05 provides separate fire alarm and fault relay contacts.
| Terminal | Function |
|---|---|
| GND | DC 24 V negative |
| 24V | DC 24 V positive |
| COM | Fire alarm relay common |
| NO | Fire alarm relay normally open |
| NC | Fire alarm relay normally closed |
| GZCOM | Fault relay common |
| GZNO | Fault relay normally open |
| GZNC | Fault relay normally closed |
| 485A | RS485 A |
| 485B | RS485 B |
The manual specifically states that the DC 24 V power input and RS485 A/B connections are polarity-sensitive.
When cables, plastics and other electrical insulation materials are heated, they may begin to decompose and release particles and gases.
The AT-AS05 monitors these overheating-related pyrolysis products in the protected electrical environment.
The manual describes electrical fire development as an early process that may involve:
Abnormal Heating → Particle/Gas Release → Odor → Visible Smoke
The detector is intended to identify the particle and gas release stage before visible smoke develops.
After power is applied, the detector enters an initialization period of approximately 2 minutes.
During initialization:
Initialization Indicator ON
After initialization:
Initialization Indicator OFF
Run Indicator ON
The detector then enters normal monitoring status.
If an internal detector fault is detected:
Fault Indicator ON
When the monitored environment reaches the alarm condition:
Alarm Indicator ON
The detector can also generate an audible alarm.
After the fault or alarm condition has been cleared, the detector can be reset through the upper-level host or commissioning tool.
According to the supplied manual, the AT-AS05 can be used in relatively enclosed electrical environments such as: