• AS05 Pyrolysis Particle Electrical Fire Monitoring Detector for Electrical Cabinets with RS485 and Relay Output
  • AS05 Pyrolysis Particle Electrical Fire Monitoring Detector for Electrical Cabinets with RS485 and Relay Output

AS05 Pyrolysis Particle Electrical Fire Monitoring Detector for Electrical Cabinets with RS485 and Relay Output

No.AT-AS05

The ANWETECH AT-AS05 Pyrolysis Particle Electrical Fire Monitoring Detector is designed for early electrical fire monitoring inside electrical cabinets and other relatively enclosed electrical equipment spaces.

It monitors pyrolysis particles and gases generated when electrical cables, insulation materials and electrical components begin to overheat. According to the product manual, the detector can provide an alarm before visible smoke is produced, helping identify abnormal heating at an early stage.

The AT-AS05 supports RS485 communication, fire alarm relay output and fault relay output, allowing integration with an upper-level monitoring system.

  • AS05 Pyrolysis Particle Electrical Fire Monitoring Detector for Electrical Cabinets with RS485 and Relay Output

Description

Product Overview

Electrical faults do not always begin with immediate flame or visible smoke. In many cases, electrical cables, insulation materials, switches and other electrical components first experience abnormal heating.

During this early stage, heated materials may decompose and release very small pyrolysis particles and gases.

The AT-AS05 is designed to monitor these changes and provide early warning before visible smoke develops.

The detector is specified for monitoring particles and gases generated by overheating of materials and electrical equipment including:

  • PVC insulated cables
  • ABS materials
  • Epoxy glass-fiber laminates
  • Batteries
  • Circuit breakers
  • Load switches
  • Other electrical equipment specified in the product manual

The manual states that the detector can monitor pyrolysis particles with a diameter range of approximately 1 nm to 10 nm.

This makes the AT-AS05 suitable for early electrical fire monitoring in electrical cabinets and other relatively enclosed electrical equipment environments.


Key Features

Early Electrical Overheating Detection

The detector monitors particles and gases generated when electrical insulation materials and electrical equipment begin to overheat.

It is designed to provide warning before visible smoke appears.

Pyrolysis Particle Monitoring

The specified monitored pyrolysis-particle diameter range is:

1 nm–10 nm

This allows the detector to monitor products generated during the early overheating stage of electrical materials.

Designed for Electrical Cabinets

The product manual lists applications including:

  • High-voltage distribution cabinets
  • Low-voltage distribution cabinets
  • Power transmission switchgear
  • Server cabinets
  • Generator cabinets
  • Energy storage cabinets
  • Battery compartments

It can also be used in other relatively enclosed electrical spaces specified in the manual.

RS485 Communication

The AT-AS05 supports RS485 communication with an upper-level host system.

Supported baud rates:

2400 bps, 4800 bps, 9600 bps, 19200 bps

Default baud rate:

9600 bps

Default RS485 address:

01

Fire Alarm Relay Output

The detector provides a dedicated fire alarm relay:

3 A @ 30 VDC

Normally Open and Normally Closed contacts are available.

Fault Relay Output

A separate fault relay is also provided:

3 A @ 30 VDC

Normally Open and Normally Closed contacts are available.

Local Audible and Visual Alarm

When an alarm condition is detected, the detector alarm indicator remains illuminated and the device can provide an audible alarm.

The audible alarm can be enabled or disabled through the upper-level host system.

Adjustable Temperature Alarm Threshold

Default temperature alarm threshold:

90°C

Adjustable range:

55°C–120°C

Wide DC Power Input

Rated operating voltage:

DC 24 V

Supported input range:

DC 9–36 V

Technical Specifications

Parameter Specification
Model AT-AS05
Product Type Pyrolysis Particle Electrical Fire Monitoring Detector
Rated Operating Voltage DC 24 V
Input Voltage Range DC 9–36 V
Operating Current 35 mA ± 5 mA at DC 24 V
Operating Humidity ≤95% RH
Ambient Temperature -30°C to +70°C
Pyrolysis Particle Alarm Threshold 0–1000 pyrolysis particle units
Temperature Alarm Threshold Default 90°C
Adjustable Temperature Range 55°C–120°C
Monitored Gas Hydrocarbon-chain compound gases associated with PVC cables and electrical equipment
Communication Switching signal or RS485
RS485 Communication Distance ≤1.5 km to upper-level host
Fire Alarm Relay 3 A @ 30 VDC, NO/NC selectable
Fault Relay 3 A @ 30 VDC, NO/NC selectable
Installation Magnetic mounting / Ceiling mounting
Product Dimensions 100 × 100 × 32.2 mm
Electromagnetic Compatibility According to GB16838

The technical specifications above are taken from the supplied product manual.


RS485 Communication

The AT-AS05 uses a standard RS485 interface for communication with an upper-level host.

Baud Rate Options:
2400 bps, 4800 bps, 9600 bps, 19200 bps

Default Baud Rate:
9600 bps

Default Address:
01

Maximum RS485 Communication Distance:
≤1.5 km to the upper-level host

Communication Protocol:
—

The supplied manual does not identify Modbus or another specific application-layer communication protocol. This should be confirmed separately before publishing any Modbus claim.


Relay Output and Terminal Definition

The AT-AS05 provides separate fire alarm and fault relay contacts.

Terminal Function
GND DC 24 V negative
24V DC 24 V positive
COM Fire alarm relay common
NO Fire alarm relay normally open
NC Fire alarm relay normally closed
GZCOM Fault relay common
GZNO Fault relay normally open
GZNC Fault relay normally closed
485A RS485 A
485B RS485 B

The manual specifically states that the DC 24 V power input and RS485 A/B connections are polarity-sensitive.


Working Principle

When cables, plastics and other electrical insulation materials are heated, they may begin to decompose and release particles and gases.

The AT-AS05 monitors these overheating-related pyrolysis products in the protected electrical environment.

The manual describes electrical fire development as an early process that may involve:

Abnormal Heating → Particle/Gas Release → Odor → Visible Smoke

The detector is intended to identify the particle and gas release stage before visible smoke develops.


Operating Status

After power is applied, the detector enters an initialization period of approximately 2 minutes.

During initialization:

Initialization Indicator ON

After initialization:

Initialization Indicator OFF
Run Indicator ON

The detector then enters normal monitoring status.

If an internal detector fault is detected:

Fault Indicator ON

When the monitored environment reaches the alarm condition:

Alarm Indicator ON

The detector can also generate an audible alarm.

After the fault or alarm condition has been cleared, the detector can be reset through the upper-level host or commissioning tool.


Applications

According to the supplied manual, the AT-AS05 can be used in relatively enclosed electrical environments such as:

  • Electrical cabinets
  • High-voltage distribution cabinets
  • Low-voltage distribution cabinets
  • Power transmission switchgear
  • Power distribution rooms
  • Equipment rooms
  • Substations
  • Server cabinets
  • Generator cabinets
  • Energy storage cabinets
  • Charging piles
  • Prefabricated cabins
  • Battery compartments
  • Box-type substations

Download