The ANWETECH High Pressure Water Mist Fire Extinguishing System is a fixed fire protection system that uses water as the extinguishing medium. Operating at a rated system pressure of 10–16 MPa, it produces fine water droplets through specially designed atomizing nozzles for fire suppression and extinguishment.
Available in open-nozzle and closed-nozzle configurations, the system incorporates high-pressure pump units, water storage, stainless steel components, control equipment, and dedicated water mist nozzles.
Multiple pump unit configurations are available, with rated working pressure of 14 MPa and maximum flow capacities ranging from 115 L/min to 805 L/min.
The ANWETECH High Pressure Water Mist Fire Extinguishing System provides a water-based fire protection solution for equipment and enclosed spaces.
Under specified operating pressure, normally approximately 10 MPa, high-pressure water passes through specially designed atomizing nozzles to produce fine droplets. The system is designed to provide rapid fire extinguishment, efficient smoke reduction, and prevention of fire re-ignition.
The system is available in two configurations:
Open-Nozzle Water Mist System
In an open system, fire detection and alarm equipment sends automatic linkage signals to the pump-unit control center and the applicable zone control valve group. The high-pressure pump starts, the selected zone valve opens, and water mist is discharged through the open nozzles.
Closed-Nozzle Water Mist System
In a closed system, heat-sensitive glass bulb nozzles operate when their rated operating temperature is reached. The resulting water-flow indication is used to start the high-pressure pump unit. Closed systems generally do not require a zone control valve group.
Both configurations can be selected according to the fire protection requirements and approved system design.
High-pressure water mist technology with fine atomized water droplets.
Rapid fire extinguishment and efficient smoke reduction.
Effective prevention of fire re-ignition.
Water-based extinguishing medium.
Open-nozzle and closed-nozzle configurations.
Stainless steel nine-plunger high-pressure pump.
Multiple pump configurations for different system flow requirements.
Automatic, manual, and mechanical/emergency operating modes.
Fire detection and alarm system linkage for automatic operation.
Stainless steel water mist nozzles.
Dedicated pump control cabinet and pressure-stabilizing equipment.
Zone control valve groups available for open-system configurations.
| Parameter | Specification |
|---|---|
| Brand | ANWETECH |
| Product Name | High Pressure Water Mist Fire Extinguishing System |
| System Type | Fixed high-pressure water mist system |
| System Configuration | Open or closed system |
| Extinguishing Medium | Water |
| Rated System Pressure | 10–16 MPa |
| Pump Rated Working Pressure | 14 MPa |
| Main Pump Power | 30 kW per main pump |
| Operating Temperature | 4°C to 50°C |
| Water Storage Volume | 1000 L |
| High Pressure Pump Type | Stainless steel nine-plunger pump |
| High Pressure Pump Model | AP8016C |
| Rated Flow | According to selected pump unit |
| Normal Standby Pressure | 0.8–1.2 MPa |
| Zone Control Valve Material | Stainless steel |
| Zone Control Valve Maximum Working Pressure | 16 MPa |
| Zone Control Valve Power Supply | DC24 V |
| Safety Valve Material | Stainless steel |
| Safety Valve Pressure Adjustment Range | 8–14 MPa |
| Safety Valve Maximum Allowable Flow | 120 L/min |
| Electrical Supply | Two independent dual power supplies, AC380 V |
| Implemented Standard | GA1149-2014 |
ANWETECH offers multiple high-pressure water mist pump unit configurations with different maximum flow capacities.
| Pump Unit Model | Pump Configuration | Maximum Flow | Pressure | Power |
|---|---|---|---|---|
| XSWBG-115/14 | 1 Duty + 1 Standby | 115 L/min | 14 MPa | 30 kW |
| XSWBG-230/14 | 2 Duty + 1 Standby | 230 L/min | 14 MPa | 60 kW |
| XSWBG-345/14 | 3 Duty + 1 Standby | 345 L/min | 14 MPa | 90 kW |
| XSWBG-460/14 QX1 | 4 Duty + 1 Standby | 460 L/min | 14 MPa | 120 kW |
| XSWBG-575/14 QX1 | 5 Duty + 1 Standby | 575 L/min | 14 MPa | 150 kW |
| XSWBG-690/14 QX1 | 6 Duty + 1 Standby | 690 L/min | 14 MPa | 180 kW |
| XSWBG-805/14 QX1 | 7 Duty + 1 Standby | 805 L/min | 14 MPa | 210 kW |
| Pump Unit Model | Make-up Water Connection | Outlet Connection | Dimensions (L × W × H) |
|---|---|---|---|
| XSWBG-115/14 | DN50 | DN25 | 2.30 × 1.10 × 1.92 m |
| XSWBG-230/14 | DN65 | DN32 | 2.54 × 1.10 × 1.92 m |
| XSWBG-345/14 | DN65 | DN32 | 2.82 × 1.10 × 1.92 m |
| XSWBG-460/14 QX1 | DN80 | DN40 | 3.34 × 1.10 × 2.40 m |
| XSWBG-575/14 QX1 | DN80 | DN40 | 3.58 × 1.10 × 2.40 m |
| XSWBG-690/14 QX1 | DN100 | DN50 | 3.58 × 1.10 × 2.40 m |
| XSWBG-805/14 QX1 | DN100 | DN50 | 3.86 × 1.10 × 2.40 m |
The appropriate pump configuration and rated flow are determined according to the project-specific fire protection system design.
The ANWETECH high-pressure water mist system supports open and closed water mist nozzles.
Open water mist nozzles are primarily manufactured from austenitic stainless steel. Closed water mist nozzles incorporate a heat-sensitive glass bulb for temperature-activated operation.
The atomizing nozzles produce fine water droplets with a specified DV0.9 of less than 200 μm.
| Model | K Factor | Operating Pressure | Rated Flow |
|---|---|---|---|
| XSW-T 0.5/10-JM | 0.5 | ≥10 MPa | 5 L/min |
| XSW-T 0.7/10-JM | 0.7 | ≥10 MPa | 7 L/min |
| XSW-T 1.0/10-JM | 1.0 | ≥10 MPa | 10 L/min |
| XSW-T 1.2/10-JM | 1.2 | ≥10 MPa | 12 L/min |
| XSW-T 1.5/10-JM | 1.5 | ≥10 MPa | 15 L/min |
| XSW-T 1.7/10-JM | 1.7 | ≥10 MPa | 17 L/min |
| XSW-T 2.0/10-JM | 2.0 | ≥10 MPa | 20 L/min |
| XSW-T 2.5/10-JM | 2.5 | ≥10 MPa | 25 L/min |
| Model | K Factor | Rated Flow | Operating Temperature |
|---|---|---|---|
| XSW-T 1.2/10-57°C Φ2-JM | 1.2 | 12 L/min | 57°C |
| XSW-T 1.5/10-57°C Φ2-JM | 1.5 | 15 L/min | 57°C |
| XSW-T 1.7/10-57°C Φ2-JM | 1.7 | 17 L/min | 57°C |
| XSW-T 2.0/10-57°C Φ2-JM | 2.0 | 20 L/min | 57°C |
| XSW-T 2.5/10-57°C Φ2-JM | 2.5 | 25 L/min | 57°C |
All listed closed-nozzle models have an operating pressure of ≥10 MPa.
A complete high-pressure water mist fire extinguishing system consists of:
Dedicated high-pressure water mist storage tank.
High-pressure main pump unit.
Standby pump.
Pressure-stabilizing pump.
Pump control cabinet.
Water inlet solenoid valve.
Water inlet filter.
Regulating water tank.
Water supply and high-pressure water mist piping.
Zone control valve cabinets for open-system arrangements.
Open or closed water mist nozzles.
Fire detection and alarm equipment for automatic linkage and control.
Available zone control valve models include:
XSW-FZ 15/14-JM, XSW-FZ 20/14-JM, XSW-FZ 25/14-JM, XSW-FZ 32/14-JM, XSW-FZ 40/14-JM, XSW-FZ 50/14-JM
The zone control valve group mainly includes a manual ball valve, electric zone control valve, pressure gauge, pressure switch, and electrical control equipment.
In open-nozzle systems, the connected fire detection and alarm system transmits control signals to the pump-unit control center and the relevant zone control valve group when a fire condition is detected.
The high-pressure pump starts, the corresponding zone control valve opens, and water mist is discharged through the nozzles.
In closed-nozzle systems, the heat-sensitive glass bulb operates when its rated operating temperature is reached. The resulting water-flow indication initiates pump operation.
Manual control is provided as an operating mode of the system.
Mechanical/emergency operation is also provided as described in the system operating manual.
The system incorporates an AC380 V electrical supply arrangement with two independent dual power supplies.
The stainless steel electric zone control valve operates at DC24 V.
For open-nozzle configurations, automatic operation is coordinated through the fire detection and alarm system, pump-unit control center, and zone control valve group.
For closed-nozzle configurations, pump startup is initiated by water-flow indication following operation of a temperature-sensitive nozzle.
| Installation Item | Requirement |
|---|---|
| Pump Room Space | Minimum 5 × 4 × 3 m (L × W × H), excluding configurations with more than five duty pumps plus one standby pump |
| Pump Unit Foundation | 200 mm high solid cement slab |
| System Water Supply | Two independent municipal water supplies, not less than 300 L/min |
| System Drainage | Not less than 200 L/min |
| System Power Supply | Two independent dual power supplies, AC380 V |
| Lifting Equipment | 5-ton forklift or equivalent lifting equipment |
Pump unit foundation dimensions are determined according to the selected pump-unit technical documentation.
The ANWETECH High Pressure Water Mist Fire Extinguishing System is intended for fixed fire protection applications in protected equipment and spaces.
Typical protected areas identified for project-specific system selection include:
Archives and Cultural Facilities
Archives, libraries, museums, cultural relic halls, ancient buildings, and other solid-material fire hazard areas.
Electrical and Power Facilities
Power distribution rooms, generator rooms, oil-immersed power transformer areas, oil switchgear rooms, and substations.
Communication and Control Facilities
Computer rooms, communication rooms, central control rooms, large cable rooms, cable tunnels, and cable galleries.
Industrial and Specialized Facilities
Hydraulic stations, turbine-related facilities, power generation facilities, and industrial equipment spaces, subject to the applicable environmental and system design requirements.
Kitchen Fire Protection Applications
Cooking oil and grease hazard areas identified under Class K fire applications, subject to approved system selection and design.
The system is non-explosion-proof and must not be installed in environments containing flammable gases, flammable liquids such as gasoline or alcohol, or corrosive gases.
System suitability, pump selection, flow requirements, nozzle arrangement, and protected-area zoning must be determined according to the applicable project design and approval requirements.