• Wall Mounted Fire Emergency Voice Control Panel 150W
  • Wall Mounted Fire Emergency Voice Control Panel 150W

Wall Mounted Fire Emergency Voice Control Panel 150W

No.AT-VE01
VE01 is a 150 W wall mounted fire emergency voice control panel designed for integration with fire alarm linkage systems. It provides emergency voice broadcasting, MIC paging, USB / MP3 and AUX audio input with 120 V constant-voltage speaker output and automatic fault monitoring, ideal for small and medium-size building fire emergency broadcasting and voice evacuation systems.
  • Wall Mounted Fire Emergency Voice Control Panel 150W

Description

Product Overview

AT-VE01 fire emergency broadcasting panel is composed of an area control panel, audio source module and 150 W broadcasting power amplifier. It works together with fire alarm controllers, output modules and loudspeakers to form a complete fire emergency broadcasting and voice evacuation system.

When the fire linkage controller outputs a start signal, the panel automatically switches to emergency broadcast mode and sends pre-recorded fire emergency messages or live MIC paging to the connected speakers. AT-VE01 is suitable for shopping malls, office buildings, factories, schools, hospitals and other projects that require reliable voice evacuation.


Main Features

  • Wall mounted 150 W fire emergency broadcasting and voice control panel

  • Works with fire alarm linkage controllers via 24 V start signal

  • 120 V constant-voltage speaker output for emergency broadcasting

  • Four broadcast modes: emergency audio (EMER), MIC paging, USB / MP3 playback and AUX external audio input

  • Emergency audio message can be recorded via microphone or imported via USB flash drive (up to 30 s)

  • 30-minute loop recording memory for events and operations

  • Automatic fault detection for speaker line, main power and standby power with audible and visual fault alarm

  • Overload protection: output voltage reduction under minor overload and automatic shutdown under severe overload

  • Optional communication module for data exchange with the fire linkage controller

  • Self-test function for quick panel check (indicators, buzzer and LCD backlight)

  • Clear LCD menu for EMER Radio, MIC Radio, MP3, AUX, record list, self-test and reset

  • Built-in fuse to cut off power in case of internal short-circuit

  • Natural air-cooled design, suitable for continuous operation in typical indoor environments


Technical Specifications – AT-VE01

Working Environment

  • Ambient temperature: 0 °C to 40 °C

  • Relative humidity: ≤ 95% RH, non-condensing

Electrical

  • Mains input: AC 187 V to AC 242 V

  • Speaker output: 120 VAC constant-voltage line

  • Rated output power: 150 W

  • Frequency response: 80 Hz to 8 kHz (±3 dB)

  • Harmonic distortion: ≤ 5%

  • Signal-to-noise ratio: ≥ 70 dB

Recording

  • Recording time: 30 minutes loop recording

Mechanical

  • Installation type: wall mounted

  • Approximate dimensions: 318 mm × 245 mm × 127 mm (including front part about 39 mm)

Wiring and Interfaces

  • Speaker line: twisted pair cable, cross-section ≥ 1.5 mm², insulation to ground > 20 MΩ; 120 V constant-voltage speakers with internal DC isolation capacitor 1 µF / 250 V

  • Main power input: fire-fighting AC 220 V power supply

  • Backup power input: stand-by AC 220 V fire-fighting power supply

  • Emergency start input: 24 V signal from fire alarm linkage controller

  • Speaker output: connect to constant-voltage loudspeakers

  • Communication port: optional protocol conversion module

  • MIC input: microphone for live paging and recording

  • AUX input: 3.5 mm audio input for external audio source

  • USB port: USB flash drive for MP3 playback and emergency message import


Applications

Suitable for small and medium-size fire emergency broadcasting zones, including:

  • Retail shops and small shopping centres

  • Office floors and commercial buildings

  • Small plants and warehouses

  • Schools, training centres and clinics